W. White, H. Hughes, S. Singh
Dec 1, 1983
Citations
11
Citations
Quality indicators
Journal
Laboratory animal science
Abstract
The effectiveness of a cubicle containment system in preventing gaseous and particulate cross-contamination in animal facilities was evaluated using several techniques. Using a nitrous oxide dilution technique, no airborne cross-contamination was found between cubicles as long as all cubicle doors were kept closed. If the doors to the cubicle in which the gas was released were partially or completely opened, low concentrations of nitrous oxide could be detected in adjacent cubicles. These concentrations increased when the air exchange rates in the cubicle were decreased. Similar results were obtained when particulate transfer was measured using aerosolized Staphlococcus epidermidis and a slit to agar sampling technique. Air flows and point air velocities within the cubicle and the animal room were also studied. A trial of Sendai virus transmission between cubicles revealed no intercubicle transmission after 3 weeks of exposure. Overall, the cubicle containment system appeared to be an effective means of achieving limited biohazard containment, applicable to many research housing needs.